8 Troubleshooting

YASKAWA TOEP YEACOM 07A 1000-Series Option PROFINET SI-EP3 Installation Manual

47

Figure 21

Figure 22 bUS Error Delay Timing Example

Related Parameters

Table 11 Parameters related to bUS Error Auto-Reset Functionality

No.

(Addr. Hex)

<2> If F6-01 is set to 3, then the drive will continue to operate when a bUS error is detected. Use caution and proper

safety measures, when installing an emergency stop switch.

<5> The availability of this feature/function depends on drive model, software version and Profinet firmware version.

Refer to

Table 15

for specifics relating to your drive.

Name

Description

Default

F6-01

(03A2)

Operation Selection after
Communications Error

Determines drive response when a bUS error is
detected during communications with the option.
0: Ramp to Stop
1: Coast to Stop
2: Fast-Stop
3: Alarm Only

<2>

4: Alarm (d1-04)

<5>

5: Alarm Ramp to Stop

<5>

1

F6-14

<5>

(03BB)

bUS Error Auto Reset

0: Disabled
1: Enabled

0

F7-16

<5>

(03F4)

Communication Loss Timeout

Sets the timeout value for communication loss
detection in tenths of a second.
A value of 0 disables the connection timeout.
Example: An entered value of 100 represents 10.0
seconds.
Note: A change to this parameter setting is not
effective until main power to the drive is cycled.

0.0