8 Troubleshooting

44

YASKAWA TOEP YEACOM 07A 1000-Series Option PROFINET SI-EP3 Installation Manual

LED Operator Display

Fault Name

EF0

External fault input from option.
The alarm function for an external device has been triggered.

Cause

Corrective Action

An external fault is being sent from the upper
controller (PLC)

Remove the cause of the external fault
Reset the external fault input from the PLC device

Problem with the PLC program

Check the program used by the PLC and make the appropriate
corrections.

LED Operator Display

Fault Name

oFA00

Option fault.
Option is not properly connected.

Cause

Possible Solution

Non-compatible option connected to the drive

Connect an option that is compatible with the drive.

LED Operator Display

Fault Name

oFA01

Option fault.
Option is not properly connected.

Cause

Possible Solution

Problem with the connectors between the drive
and option

Turn the power off and check the connectors between the drive
and option.

LED Operator Display

Fault Name

oFA03

Option fault.
Option self-diagnostics error.

Cause

Possible Solution

Option hardware fault

Replace the option.

LED Operator Display

Fault Name

oFA04

Option fault.
Option flash write mode.

Cause

Possible Solution

Option hardware fault

Replace the option.