8 Troubleshooting

YASKAWA TOEP YEACOM 07A 1000-Series Option PROFINET SI-EP3 Installation Manual

45

LED Operator Display

Fault Name

to

oFA30 to oFA43

Option Fault (Port A).

Communication ID error.

Cause

Possible Solution

Option hardware fault

Replace the option.

LED Operator Display

Fault Name

oFb00

Option fault (CN5-B).
Non-compatible option is connected.

Cause

Possible Solution

Non-compatible option connected to the drive.

Connect the correct option to CN5-A.

LED Operator Display

Fault Name

oFb02

Option fault (CN5-B).
Two of the same options are connected at the same time.

Cause

Possible Solution

Options AI-A3 or DI-A3 were connected to the
CN5-B port while an option was already
connected to CN5-A.

Only one type of AI-A3 or DI-A3 option can be connected to the
drive.
The SI-EP3 option can only be connected to CN5-A.

LED Operator Display

Fault Name

oFc00

Option fault (CN5-C).
Non-compatible option is connected.

Cause

Possible Solution

Non-compatible option connected to the drive.

Connect the correct option to CN5-A.

LED Operator Display

Fault Name

oFc02

Option fault.
Option flash write mode.

Cause

Possible Solution

Options AI-A3 or DI-A3 are connected to the
CN5-B port with an option connected to CN5-A.

Only one type of AI-A3 or DI-A3 option can be connected to the
drive
The SI-EP3 option can only be connected to CN5-A