6 Option Related Drive Parameters

YASKAWA TOEP YEACOM 07A 1000-Series Option PROFINET SI-EP3 Installation Manual

25

F6-14

<3>

bUS Error Auto Reset

0: Disabled
1: Enabled

0

F7-01

to

F7-04

IP Address

Sets static IP address of the SI-EP3 option when parameter
F7-13=0.
Note: Parameter F7-01 sets the most significant octet.

192 168 1 20

F7-05

to

F7-08

Subnet Mask

Sets static Subnet Mask of network connection.
Note: Parameter F7-05 sets the most significant octet

255 255 255 0

F7-09

to

F7-12

Gateway Address

Sets static Gateway address of network connection.
Note: Parameter F7-09 sets the most significant octet.

192 168 1 1

F7-13

Address Mode at
Startup

Selects how the option address is set.
0: Static
2: DCP

2

F7-14

Duplex Mode Selection

Selects duplex mode setting.
0: Half duplex forced
1: Auto-negotiate duplex mode and communication speed
2: Full duplex forced
3: Half (port 1)/Auto (port 2)

<3>

4: Half (port 1)/Full (port 2)

<3>

5: Auto (port 1)/Half (port 2)

<3>

6: Auto (port 1)/Full (port 2)

<3>

7: Full (port 1)/Half (port 2)

<3>

8: Full (port 1)/Auto (port 2)

<3>

1

F7-15

Communication Speed
Selection

Sets the communication speed.
10: 10 Mbps
100: 100 Mbps
101: 10 (port 1)/100 Mbps (port 2)

<3>

102: 100 (port 1)/10 Mbps (port 2)

<3>

Default: 10

Range: 10;

100 to 102

F7-16

<3>

Communication Loss
Timeout

Sets the timeout value for communication loss detection in
tenths of a second.
A value of 0 disables the connection timeout.
Example: An entered value of 100 represents 10.0 seconds.

Default: 0.0 s
Min.: 0.0 s
Max.: 30.0 s

F7-23

to

F7-27

Dynamic Output
Assembly
Parameters
(SI-EP3 Firmware
Version VST800250)

Configurable outputs 1 to 5.
If a value other than 0 is assigned to parameters F7-23 to
F7-27 and F7-33 to F7-37 by the drive, that value will take
precedent over a value set by the configuration software.
If the value in the drive is 0 (default), the value from the
configuration software will be used.

0

Dynamic Output
Assembly
Parameters
(SI-EP3 Firmware
Version VST800251)

Configurable outputs 1 to 5.
If a value other than 0 is assigned in the configuration
software, those values will be used, otherwise, the values of
the drive parameters set in parameters F7-23 to F7-27 and
F7-33 to F7-37 will be used.

No.

Name

Description

Default