8 Troubleshooting

48

YASKAWA TOEP YEACOM 07A 1000-Series Option PROFINET SI-EP3 Installation Manual

Option Fault Monitors U6-98 and U6-99

The option can declare error/warning conditions via drive monitor parameters on the drive

digital operator as shown in

Table 12

.

Table 12 Option Fault Monitor Descriptions

Two drive monitor parameters, U6-98 and U6-99, assist in network troubleshooting:

• U6-98 displays the first declared fault since the last power cycle. U6-98 is only cleared

upon drive power-up.

• U6-99 displays the present option SI-EP3 status. U6-99 is cleared upon a network-issued

fault reset and upon

power-up.

If another fault occurs while the original fault is still active, parameter U6-98 retains the

original fault value and U6-99 stores the new fault status value.

Fault Condition

Fault Declared

Status Value

(U6-98/U6-99)

Description

No Fault

n/a

0

No faults.

Force Fault

EF0

3

Network sent a message to force this node to the fault
state.

Network Link
Down

BUS ERROR

1300

No network link to option board.

Network Failure

BUS ERROR

1301

Connection with PLC Timeout.

Default MAC
Address

None

1303

Factory default MAC Address programmed into the
option. Return for reprogramming.

No IP Address

None

1304

No IP Address has been programmed into the option.

No Station Name

None

1305

No Station Name has been programmed into the option.

Config Error

None

1306

Configuration error on power-up.

Init. Failure

None

1307

Initialize error on power-up.

Permanent
Communication
Loss

BUS ERROR

1308

Fatal error in MAC/PHY hardware, requires power cycle
to recover.