4 Option Components

YASKAWA TOEP YEACOM 07A 1000-Series Option PROFINET SI-EP3 Installation Manual

13

Power-Up Diagnostics

An LED test is performed each time the drive is powered up. The initial boot sequence may

take several seconds. After the LEDs have completed the diagnostic LED sequence, the

option is successfully initialized. The LEDs then assume operational conditions as shown in

Table 3

.

Table 4 Power-Up Diagnostic LED Sequence

NS
(visible
through
drive cover)

OFF

Offline or Power supply OFF

Green ON

Connected

Connection established with I/O
controller and in RUN mode.

Green

Flashing

Connected and stopped

Connection established with I/O
controller and in STOP mode.

Red

ON

BUS fault

Unrecoverable BUS fault.

Red Flashing

(1)

Lost

communication

Host communication is temporarily
lost.

Red Flashing

(2)

Lost

link

No

link detected to network.

10/100
(visible at
cable ports)

Yellow

OFF

10 Mbps is established

Yellow

ON

100 Mbps is established

LINK/ACT
(visible at
cable ports)

Green

OFF

Link is not established

Green

ON

Link is established

Green

Flashing

Link is established and there is
network activity

Sequence

Module Status (MS)

Network Status (NS)

Time (ms)

1

Green

OFF

250

2

Red

OFF

250

3

Green

OFF

-

4

Green

Green

250

5

Green

Red

250

6

Green

OFF

-

Name

Indication

Operating Status

Remarks

Color

Status