8 Troubleshooting

46

YASKAWA TOEP YEACOM 07A 1000-Series Option PROFINET SI-EP3 Installation Manual

Minor Faults and Alarms

bUS Error Auto-Reset

bUS Error Auto-Reset Function Description

bUS Error Auto-Reset when configured, allows the drive to automatically recover from a

bUS error as a result of a communication loss with the host.
A bUS Error will automatically reset under the following conditions.

• Network communication between the host and the drive is restored. (bUS error removed)

• bUS Error Auto-Reset is enabled as described in this section.

Enabling bUS Error Auto-Reset

Parameter F6-14

<1>

bUS Error Auto Reset enables the bUS Error Auto-Reset function.

F6-14 becomes available when the option is installed on the drive.

1. Set parameter F6-14 = 1:Enabled

2. Set parameter F6-01 = 0:Ramp to Stop, 1:Coast to Stop, 2:Fast-Stop

3. Set parameter F7-16 = 0.1 to 10.0 seconds (optional)
Enabling bUS Error Auto-Restart (After a Time Delay)

Parameter F7-16 Communication Loss Timeout will delay the occurrence of a bUS error

condition by the amount of time set in this parameter. F7-16 is set in tenths of seconds. The

status LEDs on the option will indicate the bUS error condition immediately upon detection

and during the F7-16 delay time. Refer to

Figure 21

.

• Set parameter F7-16 = 0.1 to 10.0 seconds (0.0 setting disables F7-16) to enable timeout

delay.

LED Operator Display

Minor Fault Name

CALL

Serial communication transmission error.
Communication is not established.

Cause

Possible Solution

Minor Fault

(H2-†† = 10)

Communication wiring is faulty, there
is a short circuit, or improper
connection

Check for wiring errors:
Correct the wiring
Remove ground shorts and reconnect loose wires

YES

Programming error on the master side

Check communications at start-up and correct
programming errors.

Communication circuitry is damaged.

Perform a self-diagnostics check
Replace the drive if the fault continues to occur

<1>

Available in SI-EP3/V firmware version VST800251 and later. Refer to

Table 15

for specifics relating to your drive

and drive software version.