2 spindle orientation – Yaskawa A1000 AC Drive Spindle Orientation User Manual

Page 10

Advertising
background image

2 Spindle Orientation

10

YASKAWA TM.A1000SW.063 Spindle Orientation A1000 Custom Software Supplement

S2-05

695h

High Frequency Slip
Compensation Gain
HF SlipComp Gain

Sets the gain for the Motor Slip Compensation at
Hi-Speed Function. Although this parameter rarely
needs to be changed, adjustments might be needed
under the following circumstances:
If the motor at constant speed is slower than the
frequency reference, increase S2-05.
If the motor at constant speed is faster than the
frequency reference, decrease S2-05.

0.0 to 2.5

0.0

Yes

– – – Y– – N

S2-06

696h

High Frequency Slip
Compensation Primary Delay Time
HF SlipComp Time

Sets the filter on the output side of the Slip
Compensation at Hi-Speed Function. Although this
parameter rarely needs to be changed, adjustments
might be needed under the following
circumstances:
-Decrease the setting when the slip compensation
response is too slow.
-Increase this setting when speed is unstable.

0 to 10000 ms

2000

Yes

– – – Y– – N

S2-07

697h

High Frequency Slip
Compensation Limit
HF SlipComp Lim

Sets the upper limit for the Slip Compensation at
Hi-Speed Function as a percentage of the motor
rated slip (E2-02).

0 to 250%

200

No

– – – Y– – N

S2-08

698h

High Frequency Slip
Compensation Selection During
Regeneration
HF SlipCompRegen

When Slip Compensation during Regeneration at
Hi-Speed is activated and a regenerative load is
applied, it might be necessary to use a dynamic
braking option (braking resistor, braking resistor
unit, or braking unit).

0: Disabled
1: Enabled (6 Hz and Above)
2: Enabled
(Compensation provided wherever possible)

0 to 2

0

No

– – – Y– – N

S2-11

699h

Motor 2 Control Mode Switchover
Frequency
HF SwOver Freq 2

Sets the frequency of switching from Closed Loop
Vector Control to V/f Control for Motor 2

This function is disabled when 0 or 400Hz is set,
the inverter runs as V/f Control when 0 is set, and
Closed Loop Vector Control when 400Hz is set.
However, OPE21 occurs when the relations among
Control Mode Switch Frequency (S2-11) and PG
Pulse per Revolution (F1-31) and Numbers of
Motor Poles (E4-04) are set higher than the
permissible input frequency of PG option.

0 to 400 Hz

400

No

– – – Y– – N

S2-12

69Ah

Motor 2 Control Mode Switchover
Bandwidth
HF CtrlModeSwBW2

Sets the hysteresis width of Control Mode Switch
for Motor 2.
Increase if shock occurs during Control Mode
switching.

2 to 100 Hz

20

No

– – – Y– – N

S2-15

69Dh

Motor 2 High Frequency Slip
Compensation Gain
HF SlipCompGain2

Sets the gain for the Motor Slip Compensation at
Hi-Speed Function for Motor 2. Although this
parameter rarely needs to be changed, adjustments
might be needed under the following
circumstances:
-If the motor at constant speed is slower than the
frequency reference, increase S2-15.
-If the motor at constant speed is faster than the
frequency reference, decrease S2-15.

0.0 to 2.5

0.0

Yes

– – – Y– – N

S2-16

69Eh

Motor 2 High Frequency Slip
Compensation Primary Delay Time
HF SlipCompTime2

Sets the filter on the output side of the Slip
Compensation at Hi-Speed Function for Motor 2.
Although this parameter rarely needs to be
changed, adjustments might be needed under the
following circumstances:
-Decrease the setting when the slip compensation
response is too slow.
-Increase this setting when speed is unstable.

0 to 10000 ms

2000

Yes

– – – Y– – N

S2-17

69Fh

Motor 2 High Frequency Slip
Compensation Limit
HF SlipComp Lim2

Sets the upper limit for the Slip Compensation at
Hi-Speed Function for Motor 2 as a percentage of
the motor rated slip (E4-02).

0 to 250%

200

No

– – – Y– – N

No.

MEMOBUS/

Modbus

Address

Name

Digital Operator Display

Description

Range

Default

Value

Change

During

Run

Control Method/

Access Level

Advertising
This manual is related to the following products: