Table 1.14 drive operational status indicators, Drive digital operator/keypad – Yaskawa E7B Drive Bypass System User Manual

Page 22

Advertising
background image

Yaskawa Electric America, Inc.

Installation Guide IG.E7B.02 Rev: 04-11

Date: 11-1-04 Page 20 of 46

Drive Digital Operator/Keypad

Drive Operational Status Indicators

The definition of the Drive operational status indicators are shown in Table 1.14.

Drive REMOTE Sequence (SEQ) and REMOTE Reference (REF) indicators

The Bypass operates differently than a stand alone Drive with regard to these two indicators. The Bypass control logic
interfaces with the Drive via terminals that would be used, in a Drive only installation, for the REMOTE Sequence (Run
Command), and REMOTE Reference (Speed Command).

Since these terminals are active and the appropriate parameters configured for the Bypass unit operation, the
REMOTE Sequence and REMOTE Reference LED’s will be lit even when the H/O/A HAND button is pressed (local
control), providing both the run and speed command from the local control panel. The control signals are “Local” to
the Drive and Bypass unit, but “Remote” from the Drive itself.

An exception to this rule occurs for the REMOTE REF indicator when serial communication is employed. See Table
1.15.

Table 1.14 Drive Operational Status Indicators

Indicator

Definition

FWD

Lit (red) when a forward run command is input. Also lit when the Drive is in “Hand” Mode.

REV

Lit (red) when a reverse run command is input.

REMOTE

SEQ

Lit (red) when set up for remote run command, see Table 1.15.

REMOTE

REF

Lit (red) when set up for remote speed command, see Table 1.15.

ALARM

Lit (red) when a fault has occurred and flashing when an alarm has occurred.

Table 1.15 Drive REMOTE Sequence (SEQ) and

REMOTE Reference (REF) Indicators

Indicator

HAND

AUTO

Analog Input

REMOTE SEQ

ON

ON

REMOTE REF

ON

ON

Serial COM Input

REMOTE SEQ

OFF

ON

REMOTE REF

OFF

ON

Advertising