Table 1.25 auto run indicator, Table 1.26 drive ready indicator, Table 1.27 auto/rem xfer status indicator – Yaskawa E7B Drive Bypass System User Manual
Page 26: Table 1.28 damper/bas status indicator

Yaskawa Electric America, Inc.
Installation Guide IG.E7B.02 Rev: 04-11
Date: 11-1-04 Page 24 of 46
Auto Run Status Indicator
Drive Ready Indicator
Auto/Rem Xfer Status Indicator
Damper/BAS Status Indicator
Table 1.25 Auto Run Indicator
Indicator Status
Description
On (Green)
The E7B_ _ _T or E7B_ _ _Y is in AUTO mode and has received a Run
command at TB1-2.
Off
The E7B_ _ _T or E7B_ _ _Y is not in AUTO mode or has not received
a Run command when in AUTO mode.
Table 1.26 Drive Ready Indicator
Indicator Status
Description
On (Green)
The Drive is ready to run or is running (no faults).
Off
The Drive has a fault that will prevent operation.
Table 1.27 Auto/Rem Xfer Status Indicator
Indicator Status
Description
On (Amber)
Auto Transfer to Bypass operation or Remote Transfer to Bypass
operation is active.
Off
Auto or Remote Transfer to Bypass are not active (Auto Transfer may
be disabled by DIP switch S2-1).
Table 1.28 Damper/BAS Status Indicator
Indicator Status
Description
On (Red)
A NC damper end switch or other BAS interlock contact at TB1-3 is
open.
Off
This function is disabled by DIP switch S2-8 or a contact closure exists
between terminals TB1-3 and TB1-9.