Table 1.1 output relays - factory defaults, Table 1.2 programmable output relay functions, Annunciation contacts – Yaskawa E7B Drive Bypass System User Manual

Page 5

Advertising
background image

Yaskawa Electric America, Inc.

Installation Guide IG.E7B.02 Rev: 04-11

Date: 11-1-04 Page 3 of 46

Annunciation Contacts

Contacts for customer use are provided and wired to TB1 and TB2 as follows for use as annunciators of Bypass unit
operation. All are 5 amp at 120 VAC contacts.

Programmable Output Relays 1, 2 and 3 may be re-programmed via DIP switches S2 and S3 on the Bypass Control
PCB A2. These relays provide form C “dry contacts” for customer use in annunciation to Building Automation Sys-
tems or general duty in other control logic circuits. Each contact is rated for 5 amps at 120 VAC.

The additional programmable output relay functions are described in the table below:

See Table 1.3 for DIP switch positions required to achieve these functions.

* Active = Relay condition during function

Table 1.1 Output Relays - Factory Defaults

Function

Name (E7L-00)

Terminal Block

Terminals

Type

Motor Run

Motor Run *

TB1

10-11

Form A

Hand Mode

Relay 1 @

TB1

12-13-14

Form C

Auto Mode

Relay 2 @

TB2

1-2-3

Form C

System Fault

Relay 3 @

TB2

4-5-6

Form C

* = Dedicated
@ = Programmable

Table 1.2 Programmable Output Relay Functions

Function

Description

Factory Default

Bypass Run

Annunciates running in Bypass mode

No

Damper Actuator

Intended to close a contact in a damper actuator circuit
whenever the motor is running (operation similar to the

dedicated “Motor Run” relay)

No

Auto Transfer

Annunciates automatic transfer to Bypass operation due to a
Drive fault

No

Drive Run

Annunciates running in Drive mode

No

Serial Com Run

Annunciates that the run command is coming from serial
communications

No

Hand Mode

Annunciates that the Drive or Bypass is being operated in
Hand (local) mode

Relay 1

Auto Mode

Annunciates that the Drive or Bypass is being operated in
Auto (remote) mode

Relay 2

System Fault

Annunciates that a Drive, motor overload or control circuit
fault has occurred

Relay 3

Table 1.3 DIP Switch Settings for Output Relay Functions

No.

Function

Programmable

Relay 1

Programmable

Relay 2

Programmable

Relay 3

Active*

Function Description

S2(6) S2(5) S2(4) S3(3) S3(2) S3(1) S3(6) S3(5) S3(4)

1

Bypass Run

OFF

OFF

OFF

OFF

OFF

OFF

OFF

OFF

OFF

ENERGIZED

Running in Bypass mode

2

Damper Coil

OFF

OFF

ON

OFF

OFF

ON

OFF

OFF

ON

ENERGIZED

Damper actuator activation

3

Auto Transfer

OFF

ON

OFF

OFF

ON

OFF

OFF

ON

OFF

ENERGIZED

Auto-Transfer is active

4

Drive Run

OFF

ON

ON

OFF

ON

ON

OFF

ON

ON

ENERGIZED

Drive is in the Run mode

5

Serial Com.

Run

ON

OFF

OFF

ON

OFF

OFF

ON

OFF

OFF

ENERGIZED

Serial Comm. Run command

6

Hand Mode

ON

OFF

ON

ON

OFF

ON

ON

OFF

ON

ENERGIZED

Manual mode operation

7

Auto Mode

ON

ON

OFF

ON

ON

OFF

ON

ON

OFF

ENERGIZED

Auto mode operation

8

System Fault

ON

ON

ON

ON

ON

ON

ON

ON

ON

DEENERGIZED Drive, motor or control fault

Factory Settings

ON

OFF

ON

ON

ON

OFF

ON

ON

ON

Advertising