Yaskawa Electric America, Inc.

Installation Guide IG.E7B.02 Rev: 04-11

Date: 11-1-04 Page 22 of 46

Control Panel Indicator Lights (LEDs)

Control Power Status Indicator

Drive Run Indicator

Bypass Run Indicator

Table 1.18 Control Power Indicator

Indicator Status

Condition

On (Green)

3

Phase Power is applied to the Bypass unit and the control power

transformer is functioning.

Off

3

Phase Power is disconnected from the Bypass unit or a control

power transformer fuse has cleared.

Table 1.19 Drive Run Indicator

Indicator Status

Condition

On (Green)

The Drive has been given a run command in HAND or AUTO mode
and the Bypass circuit is de-energized.

Off

The Drive has no run command in either the HAND or AUTO
modes. The unit may be operating in Bypass mode.

Table 1.20 Bypass Run Indicator

Indicator Status

Description

On (Amber)

The Bypass has been given a run command in the HAND or AUTO
mode.

Or, the operation has been remotely transferred to Bypass using the
“Remote Transfer to Bypass” feature via a BAS contact closure at

terminals TB1-4 and TB1-9.

Or, the operation has been automatically transferred to Bypass after a
Drive fault condition via the DIP switch selectable “Auto Transfer to
Bypass” feature (S2-1).

Or, the operation has been transferred to Bypass using the “Smoke
Purge” feature via a contact closure at terminals TB1-5 and TB1-9.

The motor is running at full speed across-the-line and the Drive is

disconnected from the motor.

Off

The Bypass has no run command in either the HAND or AUTO modes.
The unit may be operating in Drive mode.