Example of Changing a Parameter

Table 1.31 provides an example of how to change parameter “C1-01” (Acceleration Time 1) from 30 sec to 20 sec.

Table 1.31 Changing a Parameter in the Programming Menu

Step

Number

Digital Operator Display

Description

1

Power supply turned ON.

2

MENU Key pressed to enter drive menu.

3

MENU Key pressed to enter quick programming
menu.

4

MENU Key pressed to enter advanced

programming menu.

5

DATA/ENTER pressed to access monitor display.

6

INCREASE or DECREASE Key pressed to display
C1-01 (Acceleration Time 1).

7

DATA/ENTER Key pressed to access setting

display. The setting of C1-01 (30.00) is displayed.

8

Shift/RESET Key pressed to move the flashing
digit to the right.

9

DECREASE Key pressed to change set value to
20.00 s.

10

DATA/ENTER Key pressed to enter the set data.
“END” is displayed for 10 s and then the entered
value is displayed for 0.5 s.

11

The monitor display for C1-01 returns.