YASKAWA PL.P1000.01 P7 to P1000 - Product Transition Guide

13 Appendix 2 Parameter Cross Reference

13

Appendix 2 Parameter Cross Reference

‹

Parameter Setting Procedure

1.

Table 12

lists the parameter setting information needed to upgrade from P7 to a new P1000 drive.

2.

Check all P7 parameters that have been changed from their default settings by using the Modified Constants
Menu.

3.

Set parameters as described in this section.

Note: Default values in

Table 12

are listed for P1000 200 V Class 0.4 kW Drive Using V/f Control Mode.

Table 12 Parameter Cross Reference

Parameter Name

P7

P1000

Setting

Parameter

Default

Parameter

Default

P7

P1000

Environment
Settings

Language
Selection

A1-00

0

A1-00

0

A1-00

A1-00

0: English

0: English

1: Japanese

1: Japanese

2: German

2: German

3: French

3: French

4: Italian

4: Italian

5: Spanish

5: Spanish

6: Portuguese

6: Portuguese

7: Chinese

Access Level
Selection

A1-01

2

A1-01

2

A1-01

A1-01

0: Operation only
(monitors only)

0: Operation only
(monitors only)

1: User Parameters

1: User Parameters
Set parameters A2-01 to A2-32

2: All parameters

2: All parameters

Control Method
Selection

N/A

0

A1-02

0

N/A

N/A

V/f Control

V/f Control

Initialize
Parameters

A1-03

0

A1-03

0

A1-03

A1-03

0: No initialization

0: No initialization

1110: User initialize

1110: User initialize

2220: 2-wire sequence

2220: 2-wire sequence

3330: 3-wire sequence

3330: 3-wire sequence

5550: Reset oPE04
8008: Pump
8009: Pump w/ PI
8010: Fan
8011: Fan w/ PI

Password

A1-04

0

A1-04

0000

Password Setting

A1-05

0

A1-05

0000

User Parameters

A2-01 to

A2-32

A2-01 to

A2-32

If setting A1-01 to 1, refer to the manual
and set parameters A2-01 through A2-32.