13 Appendix 2 Parameter Cross Reference

42

YASKAWA PL.P1000.01 P7 to P1000 - Product Transition Guide

Stall
Prevention
Function

Stall Prevention
Level during
Run

L3-06

120%*

L3-06

120% **

*Varies by duty rating (Defaults: HD = 150%, ND = 120%)
**Upper limit is determined by parameters L8-38, Carrier
Frequency Reduction Selection.

Frequency
Detection

Speed
Agreement
Detection Level

L4-01

0.0 Hz

L4-01

0.0 Hz

Speed
Agreement
Detection Width

L4-02

2.0 Hz

L4-02

2.0 Hz

Frequency
Reference Loss
Detection
Selection

L4-05

1

L4-05

0

L4-05

L4-05

0: Stop

0: Stop

1: Run at L4-06 PrevRef

1: Run at the level set to L4-06

In P1000, the setting range for the frequency reference
when the reference is lost
(L4-06) is 0 to 100% (default: 80%)

Reference
Detection

Frequency
Reference Level
at Loss
Frequency

L4-06

80.0%

L4-06

80.0%

Fault Restart

Number of Auto
Restart Attempts

L5-01

0 times

L5-01

0 times

Auto Restart
Operation
Selection

L5-02

0

L5-02

0

L5-02

L5-02

0: No Fault Relay

0: Fault output not active

1: Fault Relay Active

1: Fault output active during
restart attempt

Maximum
Restart Time
After
Fault

L5-03

180.0 s

L5-04

10.0 s*

L5-03

L5-04

L5-05

180.0 s

180.0 s

1: Use time in
L5-04

L5-05

0*

* Use the above settings to have
the same fault reset method as the
P7 drive.

Overtorque
Detection

Torque
Detection
Selection 1

L6-01

0

L6-01

0

L6-01, L6-04

L6-01, L6-04

0: Disabled

0: Disabled

1: oL3 detection only active
during speed agree, operation
continues after detection

1: oL3 detection only active
during speed agree, operation
continues after detection

2: oL3 detection always active
during run, operation continues
after detection

2: oL3 detection always active
during run, operation continues
after detection

3: oL3 detection only active
during speed agree, output
shuts down on an oL3 fault

3: oL3 detection only active
during speed agree, output shuts
down on an oL3 fault

4: oL3 detection always active
during run, output shuts down
on an oL3 fault

4: oL3 detection always active
during run, output shuts down on
an oL3 fault

5: UL3 detection only active
during speed agree, operation
continues after detection

5: UL3 detection only active
during speed agree, operation
continues after detection

Parameter Name

P7

P1000

Setting

Parameter

Default

Parameter

Default

P7

P1000