Yaskawa P7 to P1000 User Manual

Page 45

Advertising
background image

13 Appendix 2 Parameter Cross Reference

YASKAWA PL.P1000.01 P7 to P1000 - Product Transition Guide

45

Display
Setting/
Selection

Digital Operator
Display
Selection

o1-03

0

o1-03

0

o1-03

o1-03

0: Hz units

0: 0.01 Hz units

1: % units
(100% = E1-04)

1: 0.01% units

2 to 39: RPM

2: r/min units

40 to 39999: User display

3: User-set units
o1-10

o1-11

1 to 60000

0 to 3

o1-10: Determines how the units for the frequency reference.
o1-11: Sets the decimal point for the frequency reference display
Ex. : For a max output frequency of 200.0, set the following:

Setting value :
o1-03 = 12000

Setting value: o1-03 = 3
: o1-10 = 2000
: o1-11 = 1

1 2 0 0 0
│ └ Max value, excluding decimal point → o1-10= “2000”
└── digits displayed to the right of the decimal → o1-11 = 1

LCD Brightness

o1-05

3

This parameter is not available in P1000.

User Monitor
Selection Mode

o1-06

0

o1-06

0

o2-06

o2-06

0: 3 Mon Sequential (Displays
next 2 sequential monitors)

0: 3 Mon Sequential (Displays
next 2 sequential monitors)

1: 3 Mon Selectable
(Set by 01-07 and 01-08)

1: 3 Mon Selectable
(Set by 01-07 and 01-08)

Second LIne
User Monitor
Selection

o1-07

2*

o1-07

2*

*Default setting changes to 38 when b5-01 is set to 1.

Third LIne User
Monitor
Selection

o1-08

3*

o1-08

3*

*Default setting changes to 24 when b5-01 is set to 1.

Frequency
Reference
Display Units

o1-09

0

o1-09

25

o1-09

o1-09

0: WC:InchOfWater

0: WC (inch of water)

1: PSI:lb/SqrInch

1: PSI
(pounds per square inch)

2: GPM:Gallons/Min

2: GPM
(gallons per minute)

3: F:DegFahrenheit

3: ° F (degrees Fahrenheit)

4: CFM:Cubic ft/Min

4: CFM
(cubic feet per minute)

5: CMH:Cubic M/Hr

5: CMH
(cubic meters per hour)

6: LPH:Liters/Hr

6: LPH (liters per hour)

7: LPS (liters per second)

8: Bar:Bar

8: Bar (Bar)

9: Pa:Pascals

9: Pa (Pascal)

10: C:DegCelsius

10: ° C (degrees Celsius)

11: Mtr:Meters

11: Mtr (meters)

12: Ft (feet)

13: LPM (liters per
minute)

Parameter Name

P7

P1000

Setting

Parameter

Default

Parameter

Default

P7

P1000

Advertising