13 Appendix 2 Parameter Cross Reference

40

YASKAWA PL.P1000.01 P7 to P1000 - Product Transition Guide

MEMOBUS
Comms.

Drive Node
Address

H5-01

1F

H5-01

1F

Communication
Speed Selection

H5-02

3

H5-02

3

H5-02

H5-02

0: 1200 bps

0: 1200 bps

1: 2400 bps

1: 2400 bps

2: 4800 bps

2: 4800 bps

3: 9600 bps

3: 9600 bps

4: 19200 bps

4: 19200 bps

5: 38400 bps

6: 57600 bps

7: 76800 bps

8: 115200 bps

Communication
Parity Selection

H5-03

0

H5-03

0

H5-03

H5-03

0: No parity

0: No parity

1: Even parity

1: Even parity

2: Odd parity

2: Odd parity

Stopping
Method After
Communication
Error

H5-04

3

H5-04

0

H5-04

H5-04

0: Ramp to stop

0: Ramp to stop

1: Coast to stop

1: Coast to stop

2: Fast Stop

2: Fast Stop

3: Alarm Only

3: Alarm Only

Communication
Fault Detection
Selection

H5-05

1

H5-05

0

H5-05

H5-05

0: Disabled

0: Disabled

1: Enabled

1: Enabled

Drive Transmit
Wait Time

H5-06

5 ms

H5-06

5 ms

RTS Control
Selection

H5-07

1

H5-07

1

H5-07

H5-07

0: Disabled
(RTS always on)

0: Disabled
(RTS always on)

1: Enabled
(RTS enabled during
send only)

1: Enabled
(RTS enabled during send only)

Communication
Error Detection
Time

H5-09

2.0

H5-09

2.0

Motor
Protection
Function

Motor Overload
Protection
Selection

L1-01

1

L1-01

1

L1-01

L1-01

0: Disabled

0: Disabled

1: Standard fan cooled

1: General-purpose motor

2: Standard blower cooled

2: Drive-dedicated motor with a
speed range of 1:10

3: Vector motor

3: Vector motor with a speed
range of 1:100

6: General purpose motor (50 Hz)

Motor Overload
Protection Time

L1-02

8.0 min.

L1-02

1.0 min.

Motor Overheat
Alarm Operation
Selection

L1-03

3

L1-03

3

L1-03

L1-03

0: Ramp to stop

0: Ramp to stop

1: Coast to stop

1: Coast to stop

2: Fast Stop

2: Fast Stop

3: Alarm Only

3: Alarm Only

Parameter Name

P7

P1000

Setting

Parameter

Default

Parameter

Default

P7

P1000