13 Appendix 2 Parameter Cross Reference

YASKAWA PL.P1000.01 P7 to P1000 - Product Transition Guide

43

Overtorque
Detection

Torque
Detection
Selection 1

L6-01

0

L6-01

0

6: UL3 detection always active
during run, operation continues
after detection

6: UL3 detection always active
during run, operation continues
after detection

7: UL3 detection only active
during speed agree, output
shuts down on an oL3 fault

7: UL3 detection only active
during speed agree, output shuts
down on an oL3 fault

8: UL3 detection always active
during run, output shuts down
on an oL3 fault

8: UL3 detection always active
during run, output shuts down on
an oL3 fault

9: UL6 detection only active
during speed agree, operation
continues after detection

10: UL6 detection always active
during run, operation continues
after detection

11: UL6 detection only active
during speed agree, output shuts
down on an oL3 fault

12: UL6 detection always active
during run, output shuts down on
an oL3 fault

Torque
Detection Level
1

L6-02

15%

L6-02

15%

Torque
Detection Time 1

L6-03

10.0 s

L6-03

10.0 s

Hardware
Protection

Internal
Dynamic
Braking Resistor
Protection
Selection (ERF)

L8-01

0

L8-01

0

L8-01

L8-01

0: Not Provided

0: Disabled

1: Provided

1: Enabled

Overheat
Pre-Alarm Level

L8-02

95 °C

L8-02

*

*Determined by drive capacity parameter o2-04.

Overheat Pre-
Alarm Operation
Selection

L8-03

3

L8-03

3

L8-03

L8-03

0: Ramp to stop

0: Ramp to stop

1: Coast to stop

1: Coast to stop

2: Fast Stop

2: Fast Stop

3: Alarm Only

3: Continue operation
(Alarm triggered)

4: Continue operation at reduced
speed as set in L8-19

Input Phase Loss
Detection Level

L8-06

KVA

Dep.

N/A

Output Ground
Fault Detection
Selection

L8-09

1

L8-09

1*

L8-09

L8-09

0: Disabled

0: Disabled

1: Enabled

1: Enabled

*Determined by drive capacity parameter o2-04.

Heatsink
Cooling Fan
Operation
Selection

L8-10

0

L8-10

0

L8-10

L8-10

0: During run only

0: During run only

1: Fan always on

1: Fan always on

Parameter Name

P7

P1000

Setting

Parameter

Default

Parameter

Default

P7

P1000