3 p7 to p1000 feature specifications, P7 to p1000 feature specifications – Yaskawa P7 to P1000 User Manual

Page 7

Advertising
background image

3 P7 to P1000 Feature Specifications

YASKAWA PL.P1000.01 P7 to P1000 - Product Transition Guide

7

3

P7 to P1000 Feature Specifications

Table 3 P7 to P1000 Feature Specifications

Feature

Item

P7

P1000

HP Range

200 V

240V 0.5 to 150 HP

240 V 0.75 to 175 HP

400 V

480V 0.5 to 500 HP

480 V 0.75 to 1000 HP

600 V

600 V 1.0 to 250 HP

Input Voltage

Rated Voltage

3-phase, 200-240 Vac
3-phase, 380-480 Vac

3-phase, 200-240 Vac
3-phase, 380-480 Vac
3-phase, 500-600 Vac

Motor types

Induction

Induction

PWM Carrier Frequency

Range

Refer to Appendix 1 P7 and P1000 Ratings
on page 18

Refer to Appendix 1 P7 and P1000 Ratings
on page 18

Maximum Output Frequency Hz

120 Hz

400 Hz

Keypad Design

Display

5 Line x 16 Character LCD

5 Line x 16 Character LCD

Copy Function

Yes

Yes

Digital Input Terminal

NPN/PNP

Switchable NPN/PNP

Switchable NPN/PNP

Digital output Terminal

Open Collector

0

0

Relay Output

2 x Form A, 1 x Form C

2 x Form A, 2 x Form C

Analog Output

Output Level

Two channels with independent level
selections
Channel 1:
0-10 V
Resolution: 10-bit plus sign

Channel 2:
0-10 V or –10 to +10 V
Resolution: 10 bit plus sign, or
4-20 mA
Resolution: 10-bit

Three channels with independent level
selections
Channels 1, 2 and 3:
0-10 V, or –10-+10 V
Resolution: 11 bit plus sign or
or 4-20 mA
Resolution: 10-bit plus sign

Pulse Input

Qty:

1

Input Frequency

1-32 kHz

Quick Disconnect Terminals

Type

Yes

Yes

Auto Tuning

Methods

Primary Resistance

Rotating, Stationary, Primary Resistance,
Rotational V/f

Preset Speeds

Qty.

5

17

Speed Search

Bi/Uni-Directional

Bi-Directional

Bi-Directional

Method

Current/Speed

Current/Speed Estimation

Auto Restart

Time Between
Attempts

0.5 to 600.0 sec (selectable)

0.5 to 600.0 sec (selectable)

Energy Savings Mode

Man/Auto

Man/Auto

Man/Auto

DC Injection Function

At Start/At Stop

At Start/At Stop +HSB during stop

At Start/At Stop +HSB during stop

Braking Function

DB Transistor

Built-in to 25 HP (200 V Class),
30 HP (400 V Class)

Built-in to 50 HP

Special

High Slip Braking

High Slip/Over-excitation Braking

Cooling Fan On/Off Control

Power/Run

Run Based

Selectable Always Active/During Run

Timer Function

On/Off Delay

On/Off Delay (0 to 3000 s)

On/Off Delay (0 to 3000 s)

Fault Code Additions

10 additional

10 with elapsed time stamp

Torque Limit/Current Limit/
Stall Prevention

Stall Prevention
During Accel/Run/Decel (V/f)
Software Current Limit (120%)

Stall Prevention
During Accel/Run/Decel (V/f)
Software Current Limit (120%)