13 Appendix 2 Parameter Cross Reference

44

YASKAWA PL.P1000.01 P7 to P1000 - Product Transition Guide

Hardware
Protection

Heatsink
Cooling Fan
Operation Delay
Time

L8-11

60 s

L8-11

60 s

Ambient
Temperature
Setting

L8-12

45 °C

L8-12

40 °C

Set the ambient temperature where the drive is being used.

oL2
Characteristics
Selection at Low
Speeds

L8-15

1

L8-15

1

L8-15

L8-15

0: Disabled

0: Disabled

1: Enabled

1: Enabled

Soft CLA
Selection

L8-18

1

L8-18

1

L8-18

L8-18

0: Disabled

0: Disabled

1: Enabled

1: Enabled

oH Frequency
Reference
Reduction Level

L8-19

20.0%

N/A

oH1 Detection
Selection for Fan
Failure

L8-32

1

L8-32

1

L8-32

L8-32

0: Disabled
(Fan Alarm is Displayed)

0: Fault, Ramp to Stop

1: Enabled (oH1 Fault occurs) 1: Fault, Coast to Stop

2: Fast-Stop

3: Alarm Only

4: Alarm, Run at L8-19 Rate

Hunting
Prevention
Function

Hunting
Prevention
Function
Selection

n1-01

1

n1-01

1

n1-01

n1-01

0: Disabled

0: Disabled

1: Enabled

1: Enabled

Hunting
Prevention Gain
Setting

n1-02

1.00

n1-02

1.00

High slip
Braking

High-Slip
Braking
Deceleration
Frequency Width

n3-01

5%

n3-01

5%

High-Slip
Braking Current
Limit

n3-02

150%

n3-02

120%*

*Upper limit is determined by parameters L8-38, Carrier
Frequency Reduction Selection.

High-Slip
Braking Dwell
Time at Stop

n3-03

1.0 s

n3-03

1.0 s

High-Slip
Braking
Overload Time

n3-04

40 s

n3-04

40 s

Display
Setting/
Selection

Drive Mode Unit
Monitor
Selection

o1-01

6*

o1-01

106*

*Refer to parameter H4-01 for details.

User Monitor
Selection After
Power Up

o1-02

1

o1-02

1

o1-02

o1-02

1: Frequency reference

1: Frequency reference

2: Output frequency

3: Output frequency

3: Output current

4: Output current

4: User-selected Monitor
(set by o1-01)

5: User-selected Monitor
(set by o1-01)

2: Direction

Parameter Name

P7

P1000

Setting

Parameter

Default

Parameter

Default

P7

P1000