Yaskawa VS mini J7 Series User Manual

Page 27

Advertising
background image

27

24

0118H

Frequency reference 4

Setting unit: 0.1Hz (less than 100Hz) /
1Hz (100Hz or greater)
Setting range: 0.0 ~ 400Hz

0.0Hz

65

25

0119H

Frequency reference 5

Setting unit: 0.1Hz (less than 100Hz) /
1Hz (100Hz or greater)
Setting range: 0.0 ~ 400Hz

0.0Hz

65

26

011AH

Frequency reference 6

Setting unit: 0.1Hz (less than 100Hz) /
1Hz (100Hz or greater)
Setting range: 0.0 ~ 400Hz

0.0Hz

65

27

011BH

Frequency reference 7

Setting unit: 0.1Hz (less than 100Hz) /
1Hz (100Hz or greater)
Setting range: 0.0 ~ 400Hz

0.0Hz

65

28

011CH

Frequency reference 8

Setting unit: 0.1Hz (less than 100Hz) /
1Hz (100Hz or greater)
Setting range: 0.0 ~ 400Hz

0.0Hz

65

29

011DH

Jog frequency reference

Setting unit: 0.1Hz (less than 100Hz) /
1Hz (100Hz or greater)
Setting range: 0.0 ~ 400Hz

6.00Hz

66

30

011EH

Frequency reference
upper limit

Setting unit: 1%
Setting range: 0 ~ 110%

100%

69

31

011FH

Frequency reference
lower limit

Setting unit: 1%
Setting range: 0 ~ 110%

0%

69

32

0120H

Motor rated current

Setting unit: 0.1A
Setting range: 0 ~ 120% of inverter
rated output current
Note: if set to 0%, then electronic ther-
mal motor overload is disabled.

(Note 2)

94

33

0121H

Electronic thermal motor
protection

0: Standard motor application
1: Specialized motor application
2: No electronic motor overload protec-

tion

0

94

No.

Register

No. for

Trans-

mission

Name

Description

Initial

Setting

*User

Setting

Ref.

Page

Advertising