Overtorque detection function selection (n59)

(1) To detect overtorque at accel/decel, set to 3 or 4.

(2) To continue the operation after overtorque detection, set to 1 or 3.

During detection, the operator displays “

” alarm (blinking).

(3) To halt inverter by a fault at overtorque detection, set to 2 or 4. At detection, the

operator displays “

” fault (ON).

Overtorque detection level (n60)

Sets the overtorque detection current level in units of 1%. (Inverter rated current =
100%)
Factory setting: 160%

Overtorque detection time (n61)

If the time when the motor current exceeds the overtorque detection level (n61),
the overtorque detection function operates.
Factory setting: 0.1sec.

Setting

Description

0

Overtorque detection not provided

1

Detected during speed agree, (alarm).
Operation continues after detection.

2

Detected during speed agree (fault). Operation stops during
detection.

3

Detected during running,
operation continues after detection. (alarm).

4

Detected during running,
operation stops during detection. (fault).