57

0139H

Stall prevention (current
limit) during running

Setting unit: 1%
Setting range: 30 ~ 200%
(Note): If set at 200%, this function will
not operate.

160%

92

58

013AH

Frequency detection
level

Setting unit: 0.1Hz (less than 100Hz) /
1Hz (100Hz or greater)
Setting range: 0.00 ~ 400Hz

0.0Hz

74

59

013BH

Overtorque detection

0: Overtorque detection disabled.
1: Detects only at speed agree, opera-

tion continues after detection.

2: Detects only at speed agree, output

is shut down after detection.

3: Detects during run, operation contin-

ued after detection.

4: Detects during run, output is shut

down after detection.

0

73

60

013CH

Overtorque detection
level

Setting unit: 1%
Setting range: 30 ~ 200%

160%

73

61

013DH

Overtorque detection
time

Setting unit: 0.1s
Setting range: 0.1 ~ 10.0s

0.1s

73

62

013EH

Memory selection of hold
output frequency

0: Hold output frequency is not stored.
1: Hold output frequency is stored.

0

86

63

013FH

Torque compensation
gain

Setting unit: 0.1
Setting range: 0.0 ~ 2.5

1.0

60

64

0140H

Motor rated slip

Setting unit: 0.1Hz
Setting range: 0.0 ~ 20.0Hz

(Note 2)

-

65

0141H

Motor no-load current

Setting unit: 1%
Setting range: 0 ~ 99%

(Note 2)

-

66

0142H

Slip compensation gain

Setting unit: 0.1
Setting range: 0.0 ~ 2.5

1.0

93

67

0143H

Slip compensation
primary delay time

Setting unit: 0.1s
Setting range: 0.0 ~ 25.5s

2.0s

93

68

0144H

Timeover detection
selection

0: Timeover detection enabled. (Coast

to stop)

1: Timeover detection enabled.
(Deceleration stop by deceleration

time 1)

2: Timeover detection enabled.
(Deceleration stop by deceleration

time 2)

3: Timeover detection enabled.
(Operation continues, alarm displays)
4: Timeover detection disabled.

0

-

69

0145H

Setting unit selection of
communications
frequency reference/
frequency monitor

0: 0.1Hz / 1
1: 0.01Hz / 1
2: 100% / 30000
3: 0.1% / 1

0

-

No.

Register

No. for

Trans-

mission

Name

Initial

Setting

User

Setting

Ref.

Page