Using output signals (n40) – Yaskawa VS mini J7 Series User Manual

Page 87

Advertising
background image

87

•

Communication/multi-function input terminal selection input (setting: 18)
(This function is effective when option card is installed)
Operation can be changed from communication command, or from multi-function
input terminal or digital operator command.
Run command and frequency reference from communication options are effective
when multi-function input terminal for this setting is “closed.”
Run command and frequency reference in LOCAL/REMOTE mode are effective
when “Open.”

Multi-function output terminal MA and MB functions can be changed when necessary
by setting parameter n40.

•

Terminal MA and MB functions: Set to n40

Using output signals (n40)

Setting

Name

Description

Ref page

0

Fault

Closed when inverter fault occurs.

–

1

Inverter Run

Closed when either FWD/REV command is input or
voltage is output from the inverter.

–

2

Agreed frequency

Closed when setting frequency agrees with inverter
output frequency.

88

3

Zero speed

Closed when inverter output frequency is less than
minimum output frequency.

–

4

Frequency detection

Output frequency

≥

frequency detection level (n58)

74

5

Frequency detection

Output frequency

≤

frequency detection level (n58)

74

6

Overtorque detection
(NO contact output)

—

73

7

Overtorque detection
(NC contact output)

—

73

10

Minor Fault

Closed when the alarm is indicated.

–

11

Base blocked

Closed when the inverter output is shut off.

–

12

Operation mode

Closed when “LOCAL” is selected by LOCAL/REMOTE
selection.

–

13

Inverter ready

Closed when inverter fault is not detected, and
operation is ready.

–

14

Fault restart

Closed during fault retry

–

15

In UV

Closed when undervoltage is detected.

–

16

In reverse run

Closed during reverse run.

–

17

In speed search

Closed when inverter conducts speed search.

–

18

Data output from
communication

Operates multi-function output terminal independently
from inverter operation (by MEMOBUS
communication).

–

Advertising