Yaskawa VS mini J7 Series User Manual

Page 30

Advertising
background image

30

No.

Register

No. for

Trans-

mission

Name

Initial

Setting

User

Setting

Ref.

Page

44

012CH

Monitor item selection

0: Output frequency
1: Output current

0

78

45

012DH

Monitor gain

Setting unit: 0.01
Setting range: 0.01 ~ 2.00

1.00

78

46

012EH

Carrier frequency

Set value: 1 ~ 4 carrier frequency = set
value ¥ 2.5kHz
Set value: Synchronous type of 7 ~ 9
lower limit 1kHz and upper limit 2.5 kHz

4(Note 3)

79

47

012FH

Operation selection after
momentary power loss

0: Operation does not continue.
1: Operation continues within momen-

tary power ride through time

2: Operation always continues. (No

UV1 fault detection)

0

70

48

0130H

Fault reset

Setting unit: time
Setting range: 0 ~ 10 times

0 time

75

49

0131H

Jump frequency 1

Setting unit: 0.1Hz (less than 100Hz) /
1Hz (100Hz or greater)
Setting range: 0.00 ~ 400Hz
(Note) If 0.0Hz is set, jump frequency 1
is enabled.

0.0Hz

75

50

0132H

Jump frequency 2

Setting unit: 0.1Hz (less than 100Hz) /
1Hz (100Hz or greater)
Setting range: 0.00 ~ 400Hz
(Note) If 0.0Hz is set, jump frequency 2
is disabled.

0.0Hz

75

51

0133H

Jump frequency width

Setting unit: 0.1Hz
Setting range: 0.0 ~ 25.5Hz
(Note) If 0.0Hz is set, jump frequencies
1 ~ 2 are disabled.

0.0Hz

75

52

0134H

DC injection braking
current

Setting unit: 1%
Setting range: 0 ~ 100%
(note) If 0% is set, it becomes base-
block status.

50%

76

53

0135H

DC injection braking time
at stop

Setting unit: 0.1s
Setting range: 0.0 ~ 25.5s
(Note) If 0.0s is set, this function will no
operate.

0.0s

83

54

0136H

DC injection braking time
at start

Setting unit: 0.1s
Setting range: 0.0 ~ 25.5s
(Note) If 0.0s is set, this function will not
operate.

0.0s

76

55

0137H

Stall prevention (current
limit) during decel

0: Stall prevention function is enabled

during deceleration.

1: Stall prevention function is disabled

during deceleration.

0

92

56

0138H

Stall prevention (current
limit) during accel

Setting unit: 1%
Setting range: 30 ~ 200%
(Note): If set at 200%, this function will
not operate.
(Note): For rated output range, the
operator level is automatically reduced.

170%

91