Yaskawa VS mini J7 Series User Manual

Page 32

Advertising
background image

32

1. Upper limit of setting range and initial setting are doubled at 400 class.
2. Changes depending on inverter capacity. Refer to the next page.
3. Initial setting of the model with digital operator (without volume) is 1.
Setting can be set to 0 by parameter initialization.

70

0146H

Slave address

Setting unit: 1
Setting range: 0 ~ 32

0

-

71

0147H

Baud rate selection

0: 2400 bps
1: 4800 bps
2: 9600 bps
3: 19200 bps

2

-

72

0148H

Parity selection

0: Even parity
1: Odd parity
2: No parity

0

-

73

0149H

Send waiting time

Setting unit: 1 = 1ms
Setting range: 10 ~ 65 ms

10ms

-

74

014AH RTS control

0: RTS control enabled.
1: RTS control disabled.

0

-

75

76

0: Execution completed / execution

command receive condition

1: READ execute
2: COPY execute
3: VRFY execute
4: kVA display
5: Software No. display

77

0: READ prohibited.
1: READ allowed.

78

014EH

Fault history

The 1 newest event is displayed
(Note) Setting is disabled.

-

54

79

014FH

Software No.

Lower 3 digits of software numbers are
displayed.
(Note): Setting is disabled.

-

-

No.

Register

No. for

Trans-

mission

Name

Initial

Setting

User

Setting

Ref.

Page