Automatic restart after momentary power loss (n47) – Yaskawa VS mini J7 Series User Manual

Page 70

Advertising
background image

70

At OFF: n16 (accel time 1) are used.

n17 (decel time 1)

At ON:

n18 (accel time 2) are used.
n19 (decel time 2)

Accel time
Set the time needed for output frequency to reach 100% from 0%.

Decel time
Set the time needed for output frequency to reach 0% from 100%.

(Maximum output frequency n09 = 100%)

The inverter has the ability to ride thru momentary power outages provided the control
logic power supplies are maintained.

When momentary power loss occurs, operation restarts automatically.

* Maintain the run command to continue operation after recovery from a momentary power loss.

† When 2 is selected, operation restarts if power supply voltage reaches its normal level while control

power supply is held. No fault signal is output.

Automatic restart after momentary power

loss (n47)

Setting.

Description

0

Continuous operation after momentary power loss not provided.

1*

Continuous operation after power recovery within momentary
power loss ride thru time is provided.

2*†

Continuous operation after power recovery (Fault output not
provided)