5.2 b: Application

u

b1: Operation Mode Selection

n

b1-01: Frequency Reference Selection 1

Selects the frequency reference source 1 for the REMOTE mode.

Note:

1. If a Run command is input to the drive but the frequency reference entered is 0 or below the minimum frequency, the RUN indicator

LED on the digital operator will light and the STOP indicator will flash.

2. Press the LO/RE key to set the drive to LOCAL and use the operator keypad to enter the frequency reference.

No.

Parameter Name

Setting Range

Default

b1-01

Frequency Reference Selection 1

0 to 4

1

Setting 0: Operator keypad

Using this setting, the frequency reference can be input by:
• switching between the multi-speed references in the d1-oo parameters.
• entering the frequency reference on the operator keypad.

Setting 1: Terminals (analog input terminals)

Using this setting, an analog frequency reference can be entered as a voltage or current signal from terminals A1, A2, or A3.
Voltage Input
Voltage input can be used at any of the three analog input terminals. Make the settings as described in

Table 5.5

for the input

used.

Table 5.5 Analog Input Settings for Frequency Reference Using Voltage Signals

Terminal

Signal Level

Parameter Settings

Notes

Signal Level

Selection

Function Selection

Gain

Bias

A1

0 to 10 Vdc

H3-01 = 0

H3-02 = 0

(Frequency Reference Bias)

H3-03

H3-04

-10 to +10 Vdc

H3-01 = 1

A2

0 to 10 Vdc

H3-09 = 0

H3-10 = 0

(Frequency Reference Bias)

H3-11

H3-12

Set jumper S1 on the terminal

board to “V” for voltage input.

-10 to +10 Vdc

H3-09 = 1

A3

0 to 10 Vdc

H3-05 = 0

H3-06 = 0

(Frequency Reference Bias)

H3-07

H3-08

Set DIP switch S4 on the

terminal board to “AI”.

-10 to +10 Vdc

H3-05 = 1

Drive

A1 Analog Input 1

0 to 10 V

AC Analog input common

2 k

+V 10.5 V, 20 mA power supply

A2 Analog Input 2

A3 Analog Input 3

Drive

A1 Analog Input 1

AC Analog input common

+V 10.5 V, 20 mA power supply

A2 Analog Input 2

A3 Analog Input 3

4 k

-10 to 10 V

OR

Customer
+/- 10 V
Supply

+10 V

-10 V

Common

Figure 5.1 Setting the Frequency Reference as a Voltage Signal at Terminal A1

Current Input
Input terminals, A1, A2, and A3 can accept a current input signal. Refer to

Table 5.6

for an example to set terminal A2 for

current input.

5.2 b: Application

YASKAWA SIEP YAIP1U 01B AC Drive - P1000 Technical Manual

147

5

Parameter Details