Yaskawa AC Drive-P1000 Industrial Fan User Manual
Page 175
Advertising

Reducing this setting increases the response time. If the filter time is too short, the motor may become unstable with a lighter
load.
No.
Name
Setting Range
Default
b8-05
Power Detection Filter Time
0 to 2000 ms
20 ms
n
b8-06: Search Operation Voltage Limit
Sets the voltage limit for the Speed Search optimal output voltage detection as a percentage of the maximum output voltage.
The drive will keep the output voltage above this level during the search operation to prevent motor stalling.
No.
Name
Setting Range
Default
b8-06
Search Operation Voltage Limit
0 to 100%
0%
5.2 b: Application
YASKAWA SIEP YAIP1U 01B AC Drive - P1000 Technical Manual
175
5
Parameter Details
Advertising