B3: speed search, Or short circuit braking, For details – Yaskawa AC Drive-P1000 Industrial Fan User Manual

Page 153: Refer to b2-03: dc injection braking time at, Or speed search

Advertising
background image

n

b2-01: DC Injection Braking Start Frequency

Active when “Ramp to Stop” is selected as the stopping method (b1-03 = 0).

No.

Name

Setting Range

Default

b2-01

DC Injection Braking Start Frequency

0.0 to 10.0 Hz

0.5 Hz

V/f Control

Sets the starting frequency for DC Injection Braking at Stop. When the output frequency falls below the setting of b2-01, DC

Injection Braking is enabled for the time set in parameter b2-04.

Output

Frequency

Time

b2-04

DC Injection

Braking

E1-09 Min. Frequency
b2-01 Zero Speed Level

Figure 5.8 DC Injection Braking at Stop for V/f

Note:

If b2-01 is set to a smaller value than E1-09 (Minimum Frequency), then DC Injection Braking will begin when the frequency falls to the

E1-09 value.

n

b2-02: DC Injection Braking Current

Sets the DC Injection Braking current as a percentage of the drive rated current. The carrier frequency is automatically reduced

to 1 kHz when this parameter is set to more than 50%.

No.

Name

Setting Range

Default

b2-02

DC Injection Braking Current

0 to 100%

50%

n

b2-03: DC Injection Braking Time at Start

Sets DC Injection Braking time at start. Disabled when set to 0.00 s.

No.

Name

Setting Range

Default

b2-03

DC Injection Braking Time at Start

0.00 to 10.00 s

0.00 s

n

b2-04: DC Injection Braking Time at Stop

Sets DC Injection Braking time at stop.

No.

Name

Setting Range

Default

b2-04

DC Injection Braking Time at Stop

0.00 to 10.00 s

0.50 s

u

b3: Speed Search

The Speed Search function allows the drive to detect the speed of a rotating motor shaft that is driven by external forces and

start the motor operation directly from the detected speed without first stopping the machine.
Example: When a momentary loss of power occurs, the drive output shuts off and the motor coasts. When power returns, the

drive can find the speed of the coasting motor and restart it directly.
For induction motors, the drive offers two types of Speed Search than can be selected by parameter b3-24 (Speed Estimation

and Current Detection). Both methods are explained below and followed by a description of all relevant parameters.

n

Current Detection Speed Search (b3-24 = 0)

Current Detection Speed Search detects the motor speed by looking at motor current in IM motors. When Speed Search is

started it reduces the output frequency starting from either the maximum output frequency or the frequency reference while

increasing the output voltage using the time set in parameter L2-04. As long as the current is higher than the level set to b3-02,

the output frequency is lowered using the time constant set to b3-03. If the current falls below b3-02, the drive assumes that

the output frequency and motor speed are the same and accelerates or decelerates to the frequency reference.
Be aware that sudden acceleration may occur when using this method of Speed Search with relatively light loads.

Figure 5.9

illustrates Current Detection Speed Search operation after a momentary power loss (L2-01 must be set to 1 or 2):

5.2 b: Application

YASKAWA SIEP YAIP1U 01B AC Drive - P1000 Technical Manual

153

5

Parameter Details