H6-08: Pulse Train Input Minimum Frequency
Sets the minimum output frequency detected by the pulse train input. Increasing this setting reduces the time the drive needs
to react to changes in the input signal.
• The pulse input value becomes 0 when the pulse input frequency falls below this level.
• Enabled when H6-01 = 0, 1, or 2.
• When simple speed feedback in V/f Control is set as the function for terminal RP (H6-01 = 3), the minimum frequency
becomes the detection time for PG disconnect (F1-14).
No.
Name
Setting Range
Default
H6-08
Pulse Train Input Minimum Frequency
0.1 to 1000.0 Hz
0.5 Hz