B.8 L: Protection Function

L parameters provide protection to the drive and motor, including control during momentary power loss, Stall Prevention,

frequency detection, fault restarts, overtorque detection, and other types of hardware protection.

u

L1: Motor Protection

No.

(Addr.

Hex)

Name

Description

Values

Page

L1-01

(480)

Motor Overload Protection

Selection

0: Disabled

1: General purpose motor (standard fan cooled)

2: Drive dedicated motor with a speed range of 1:10

3: Vector motor with a speed range of 1:100

6: General purpose motor (50 Hz)

The drive may not be able to provide protection when using multiple motors,

even if overload is enabled in L1-01. Set L1-01 to 0 and install separate thermal

relays to each motor.

Default: 1

Range: 0 to 6

233

L1-02

(481)

Motor Overload Protection

Time

Sets the motor thermal overload protection (oL1) time.

Default: 1.0 min

Min.: 0.1

Max.: 5.0

235

L1-03

(482)

Motor Overheat Alarm

Operation Selection

(PTC input)

Sets operation when the motor temperature analog input (H3-02, H3-10, or

H3-06 = E) exceeds the oH3 alarm level.

0: Ramp to stop

1: Coast to stop

2: Fast Stop (decelerate to stop using the deceleration time in C1-09)

3: Alarm only (“oH3” will flash)

Default: 3

Range: 0 to 3

236

L1-04

(483)

Motor Overheat Fault

Operation Selection

(PTC input)

Sets stopping method when the motor temperature analog input (H3-02,

H3-10, or H3-06 = E) exceeds the oH4 fault level.

0: Ramp to stop

1: Coast to stop

2: Fast Stop (decelerate to stop using the deceleration time in C1-09)

Default: 1

Range: 0 to 2

236

L1-05

(484)

Motor Temperature Input

Filter Time (PTC input)

Adjusts the filter for the motor temperature analog input (H3-02, H3-10, or

H3-06 = E).

Default: 0.20 s

Min.: 0.00

Max.: 10.00

237

L1-13

(46D)

Continuous Electrothermal

Operation Selection

0: Disabled

1: Enabled

2: Enabled (RTC)

Default: 1

Range: 0 to 2

237

u

L2: Momentary Power Loss Ride-Thru

No.

(Addr.

Hex)

Name

Description

Values

Page

L2-01

(485)

Momentary Power Loss

Operation Selection

0: Disabled. Drive trips on Uv1 fault when power is lost.

1: Recover within the time set in L2-02. Uv1 will be detected if power loss is

longer than L2-02.

2: Recover as long as CPU has power. Uv1 is not detected.

3: KEB deceleration for the time set to L2-02.

4: KEB deceleration as long as CPU has power.

5: KEB deceleration to stop.

Default: 2

Range: 0 to 5

239

L2-02

(486)

Momentary Power Loss

Ride-Thru Time

Sets the Power Loss Ride-Thru time. Enabled only when L2-01 = 1 or 3.

Default:

<1>

Min.: 0.0 s

Max.: 25.5 s

244

L2-03

(487)

Momentary Power Loss

Minimum Baseblock Time

Sets the minimum wait time for residual motor voltage decay before the drive

output reenergizes after performing Power Loss Ride-Thru.

Increasing the time set to L2-03 may help if overcurrent or overvoltage occur

during Speed Search or during DC Injection Braking.

Default:

<1>

Min.: 0.1 s

Max.: 5.0 s

244

L2-04

(488)

Momentary Power Loss

Voltage Recovery Ramp

Time

Sets the time for the output voltage to return to the preset V/f pattern during

Speed Search.

Default:

<1>

Min.: 0.0 s

Max.: 5.0 s

245