B.10 o: Operator-Related Settings

The o parameters set up the digital operator displays.

u

o1: Digital Operator Display Selection

No.

(Addr.

Hex)

Name

Description

Values

Page

o1-01

(500)

Drive Mode Unit Monitor

Selection

Selects the content of the last monitor that is shown when scrolling through

Drive Mode display. Enter the last three digits of the monitor parameter

number to be displayed: Uo-oo.

Default: 106

(Monitor U1-06)

Range: 104 to 809

266

o1-02

(501)

User Monitor Selection after

Power Up

1: Frequency reference (U1-01)

2: Direction

3: Output frequency (U1-02)

4: Output current (U1-03)

5: User-selected monitor (set by o1-01)

Default: 1

Range: 1 to 5

266

o1-03

(502)

Digital Operator Display

Selection

Sets the units the drive should use to display the frequency reference and motor

speed monitors.

0: 0.01 Hz

1: 0.01% (100% = E1-04)

2: r/min (calculated using the number of motor poles setting in E2-04)

3: User-selected units (set by o1-09, o1-10 and o1-11)

Default: 0

Range: 0 to 3

266

o1-06

(517)

User Monitor Selection

Mode

Selects the monitors displayed on the second and third lines of the digital

operator display.

0: 3 Monitor Sequential (displays the next two sequential monitors)

1: 3 Monitor Selectable (set by o1-07 and o1-08)

Default: 0

Range: 0, 1

266

o1-07

(518)

Second Line Monitor

Selection

Selects the monitor that is shown in the second line.

Enter the last three digits of the monitor parameter number to be displayed:

Uo-oo. For example, set "403" to display monitor parameter U4-03.

Note:

Parameter is effective only when o1-06 is set to 1.

Default: 102

Range: 101 to 799

266

o1-08

(519)

Third Line Monitor

Selection

Selects the monitor that is shown in the third line.

Enter the last three digits of the monitor parameter number to be displayed:

Uo-oo. For example, set "403" to display monitor parameter U4-03.

Note:

Parameter is effective only when o1-06 is set to 1.

Default: 103

Range: 101 to 799

266

o1-09

(51C)

Frequency Reference

Display Units

Sets unit display for the frequency reference parameters and frequency related

monitors when o1-03 = 3.

0: WC (Inch of water)

1: PSI (Pounds per square inch)

2: GPM (Gallons per minute)

3: F (Degrees Fahrenheit)

4: CFM (Cubic feet per minute)

5: CMH (Cubic meters per hour)

6: LPH (Liters per hour)

7: LPS (Liters per second)

8: Bar (Bar)

9: Pa (Pascal)

10: C (Degrees Celsius)

11: Mtr (Meters)

12: Ft (Feet)

13: LPM (Liters per minute)

14: CMM (Cubic meters per minute)

15: “Hg (inches of mercury)

24: Custom units (determined by o1-13 to o1-15)

25: None

Default: 25

Range: 0 to 15; 24,

25

266

o1-10

(520)

User-Set Display Units

Maximum Value

These settings define the display values when o1-03 is set to 3.

o1-10 sets the display value that is equal to the maximum output frequency.

o1-11 sets the position of the decimal position.

Default:

<1>

Range: 1 to 60000

267

o1-11

(521)

User-Set Display Units

Decimal Display

Default:

<1>

Range: 0 to 3

268

o1-13

(3105)

Frequency Reference and

Frequency Related Monitor

Custom Units 1

Sets the first character of the customer-specified unit display when o1-03 is

set to 3 and o1-09 is set to 24.

Default: 41

Range: 30 to 7A

268

o1-14

(3106)

Frequency Reference and

Frequency Related Monitor

Custom Units 2

Sets the second character of the customer-specified unit display when o1-03

is set to 3 and o1-09 is set to 24.

Default: 41

Range: 30 to 7A

268