5.10 o: Operator Related Settings

These parameters control the various functions, features, and display of the digital operator.

u

o1: Digital Operator Display Selection

These parameters determine the data display on the digital operator.

n

o1-01: Drive Mode Unit Monitor Selection

The frequency reference display appears when the drive is powered up. Pressing the up arrow key will display the following

data: frequency reference → rotational direction → output frequency → output current → o1-01 selection.
Parameter o1-01 selects the content of the last monitor in this sequence.

No.

Name

Setting Range

Default

o1-01

Drive Mode Unit Monitor Selection

104 to 809

106 (U1-06)

n

o1-02: User Monitor Selection after Power Up

Selects which monitor parameter is displayed upon power up.

Refer to U: Monitor Parameters on page 285

for a list of

monitors.

No.

Name

Setting Range

Default

o1-02

User Monitor Selection after Power Up

1 to 5

1

Setting 1: Frequency Reference (U1-01)

Setting 2: Motor Direction

Setting 3: Output Frequency (U1-02)

Setting 4: Output Current (U1-03)

Setting 5: User-selected Monitor (Set by o1-01)

n

o1-03: Digital Operator Display Selection

Sets the units used to display the frequency reference and output frequency. Set o1-03 to 3 for user-set units before setting

parameters o1-10 and o1-11.

No.

Name

Setting Range

Default

o1-03

Digital Operator Display Selection

0 to 3

0

Setting 0: 0.01 Hz units

Setting 1: 0.01% units (100% = max. output frequency)

Setting 2: r/min units (calculated by the max output frequency and the no. of motor poles)

Setting 3: User-set units (set by o1-09, o1-10, o1-11)

Set the value used for the maximum frequency reference to o1-10. Set the placement of the decimal point in this number to

o1-11.
For example, to have the maximum output frequency displayed as “100.00”, set o1-10 to 1000 and o1-11 to 2 (i.e., 1000 with

2 decimal points).

Note:

1. Parameter o1-03 allows the programmer to change the units used in the following parameters and monitors:

U1-01: frequency reference

U1-02: output frequency

U1-16: output frequency after softstarter (accel/decel ramp generator)

d1-01 to d1-17: frequency references

2. Setting o1-03 to 2 requires entering the number of motor poles to E2-04.

n

o1-06: User Monitor Selection Mode

Select between standard sequential monitors or selectable monitors to be displayed on the 2nd and 3rd lines of the digital

operator display.

5.10 o: Operator Related Settings

266

YASKAWA SIEP YAIP1U 01B AC Drive - P1000 Technical Manual