Amprobe DM-4 Power-Quality-Recorder User Manual

Page 28

Advertising
background image

27

DM-4 Power Quality Recorder

Symbols

Description

Advised Settings

ANOM REC.

Enable = the Instrument will record Voltage Sag, Surge,

and voltage spike

Disable = the instrument will not record any voltage

Sag, Surge, and voltage spike.

V1, V2, V3

V12, V23 or

V32, V31

RMS value of the voltage of phase 1, phase 2, phase 3

respectively, values of the phase-to-phase voltages 1-2,

2-3 or 3-2 and 3-1.

Single phase: V1

3 wires V12 V32 V31

4 wires V1, V2, V3

Thd, DC, 01...51 Voltage Total Harmonic Distortion, DC Component,

01..51 Harmonics respectively

Thd,01,03,05,07

Vref (Only if

ANOM. REC flag

has been enable)

RMS reference value for Voltage used in Voltage

Anomalies detection (Voltage Sag and Surge).

The Reference is:

a) Voltage Phase to Neutral for Single Phase and 4

wires three phase system

b) Voltage Phase to Phase for 3 wires three phase system

Single phase: 230V

3 wires: 400V

4 wires: 230V

LIM+, LIM-

(Only if ANOM.

REC flag has

been set ON)

High and Low Voltage Percent threshold used in

Voltage Anomalies detection (Voltage Sag and Surge).

Example: Three Phase System 4 wires.

Vref = 120, LIM+= 10%, LIM-=10% =>

High Lim = 132V, Low Lim = 108.0V

The Instrument will detect a voltage Anomalies if the

RMS Voltage Values (calculated every 14ms) beyond

the above calculated thresholds

Single phase: 120V

3 wires: 480V

4 wires 277V

I1, I2, I3, IN

RMS value of the current of phase 1, phase 2, phase 3

and of the neutral respectively.

Single phase: I1

3 wires: I1, I2, I3

4 wires I1, I2, I3, IN

Thd, DC, 01..51 Current Total Harmonic Distortion, DC Component,

01..51 Harmonics respectively

T

hd,01,03,05,07

Pt, P1, P2, P3,

P12, P32, P31

Values of the active power (total, of phase 1, phase 2

and phase 3) (only for 3 wires measurement)

value of the power measured by the Wattmeter 1-2 and

3-2 respectively.

Single phase: P1

3 wires: Pt

4 wires Pt, P1, P2, P3