13.1.6 Measurement of Harmonics

13.1.7 Temperature Drift

Temperature drift: 0.1 x accuracy/K

13.1.8 Safety

Insulation: Class 2

Pollution: 2

Over-voltage category: CAT III 600V~ (Phase-phase)

CAT II 1000V~ (Phase-Phase)

43

DM-4 Power Quality Recorder

Voltage

Range

Accuracy

Resolution

DC – 25h

26h – 33h

34h – 51h

±(5.0%+2digit)

±(10.0%+2digit)

±(15.0%+2digit)

0.1V

The voltage harmonics will be null under the following threshold:

- DC: if <1V or <2% of 1st harmonic

- 1st harmonic: if <2V

- 2nd - 51st: if <1V or <2% 1st harmonic

Current

Range

Accuracy

Resolution

DC – 25h

26h – 33h

34h – 51h

±(5.0%+2digit)

±(10.0%+2digit)

±(15.0%+2digit)

0.1A

The voltage harmonics will be null under the following threshold:

- DC: if <2% of 1st harmonic or < 0,2% of clamp full scale

- 1st harmonic: if < 0,2% of clamp full scale

- 2nd - 51st: if<2% 1st harmonic or < 0,2% of clamp full scale

Setting the FLEX option 3000A CT the DC component will be ignored.