5 reset, Recorder config – Amprobe DM-4 Power-Quality-Recorder User Manual

Page 30

Advertising
background image

5.5.5 RESET (

PRESS AND HOLD RESET KEY WHILE PRESSING ON RECORD

)

This option re-establishes the default settings of the instrument.

The default settings of the instrument consist of:

ANALYZER CONFIG:

Frequency: 60Hz

Full scale of the clamps: 1000A

Type of electrical system: 4 wires

RECORDER CONFIG:

Start: Manual (the recording is started at 00 sec mark on clock after pressing the RECORD key)

Stop: Manual

Integration period: 5S

Recording of harmonics: ON

Recording of Sag and Surge: OFF

Voltage Reference for Sag and Surge detection: 480V

Upper Limit for Sag and Surge detection: 10%

Lower Limit for Sag and Surge detection: 10%

Selected voltages: V1, V2, V3

Selected voltage harmonics:

Selected currents: I1, I2, I3, IN

Selected current harmonics:

Powers, Pf and cosΘ

Θ

selected:

Pt, P1, P2, P3

Qt, Q1, Q2, Q3

Qt, Q1, Q2, Q3

St, S1, S2, S3

Pft, Pf1, Pf2, Pf3

dpft, dpf1, dpf2, dpf3

Energies:

Eat, Ea1, Ea2, Ea3

Erit, Eri1, Eri2, Eri3

Erct, Erc1, Erc2, Erc3

Est, Es1, Es2, Es3

Note: The RESET command will not erase the instrument’s memory.

29

DM-4 Power Quality Recorder

Advertising