Technical specifications – Amprobe DM-4 Power-Quality-Recorder User Manual

Page 42

Advertising
background image

13. TECHNICAL SPECIFICATIONS

13.1 FEATURES

The accuracy is stated as [1% of the reading ± number of 2 digits]. It refers to the

following atmospheric conditions: temperature 73°F± 2°F (23°C ± 1°C) with rela-

tive humidity < 75%.

41

DM-4 Power Quality Recorder

13.1.1 Voltage Measurement

Range

Accuracy

Resolution

Input Impedance

20-370V

±(3%+2digit)

0.1V

300kΩ (phase-neutral)

310-635V

0.1V

600kΩ (phase-phase)

13.1.2 Voltage Anomalies Detection (Manual Selection of Range) Voltage

Range

Accuracy

Resolution

Input Impedance

20-370V

±(3%+2digit)

0.1V

300kΩ (phase-neutral)

310-635V

0.1V

600kΩ (phase-phase)

Time

Accuracy (ref. to 60Hz)

Resolution

±8.33ms (

1/2

period of fundamental) 8.33ms (

1/2

period of fundamental)

13.1.3 Current Measurement (Using external transducer)

Range

Accuracy Resolution

Input

Impedance

Protection against

overloads

0.005-0.26V ±(2%+2digit)

100kΩ

5V

0.26-1V

Minimal Current measurable is equal to 0.5% of Clamp Full Scale

Advertising