Amprobe AMB-110 Insulation-Resistance-Tester User Manual

Page 22

Advertising
background image

17

Displayed symbols:

INSULATION RESISTANCE

Name of selected function

SETTING PARAMETERS:

Unominal

5000 V

Set test voltage –25 V steps

Timer

5min 00s

Duration of the measurement

Timer on/off

ON

ON: timer enabled, OFF: timer disabled

Time1

01min 00s

Time to accept and display first Rmin and Rmax results

Graph R(t)

ON

Enable/Disable Graph R(t)

Timer and Time1 are independent timers. Maximum time for each of them is 30 min 60 s.

Enable/Disable the graph R(t) and Set-up the graph R(t) parameters in the Insulation Resistance
function:

• Press the SELECT key, Set-up menu appears on display, see the Fig. 12.
• Select the parameter Graph R(t) to be set using the and keys;
• Enable/Disable the graph R(t) using the and keys.
• Press the SELECT key to Set-up the parameters of the graph R(t), see the Fig. 13. Press the ESC

key to return to basic Set-up menu in the Insulation Resistance function.

• Complete the set-up adjustments pressing either the ESC key or START/STOP key (to run the

measurement directly). The last displayed settings are stored.

Fig. 12 Set-up menu in Insulation

Resistance measurement

Fig. 13 Set-up menu of the

Graph R(t)

Note

• If the Timer is OFF is not possible to Enable the Graph R(t).
• The time duration of Graph R(t) is equal to the value of Timer.
- The Timer value could be very long (up to 99 minutes), so the Special automatic decimation

algorithm is use to write the Graph R(t) to the LCD.

• The cursors of the Graph R(t) could be activated with key
• The cursors of the Graph R(t) could be moved with and keys.

Warning!

• Refer to Warnings chapter for safety precautions!