ProSoft Technology MVI69-103M User Manual
Page 107

Reference MVI69-103M
♦ CompactLogix or MicroLogix Platform
IEC 60870-5-103 Master Communication Module
ProSoft Technology, Inc.
Page 107 of 131
November 3, 2008
Fun
128 160 176 192 254 255
Inf Description
GI Type
t(z) l>>
∆l
T
∆l
L
GEN GLB
70 trip
L
2
2 X X X X
71 trip
L
3
2 X X X X
72
trip l>> (back-up operation)
4
X
73
fault location X in ohms
2
X
X
74
fault forward/line
2
X
X
75
fault reverse/busbar
2
X
X
76
teleprotection signal transmitted
2
X
X
77
teleprotection signal received
2
X
X
78
zone 1
2
X
79
zone 2
2
X
80
zone 3
2
X
81
zone 4
2
X
82
zone 5
2
X
83
zone 6
2
X
84
general
start/pick-up
X 2 X X X X
85
breaker failure
2
X
X
86
trip measuring system L
1
2
X
87
trip measuring system L
2
2
X
88
trip measuring system L
3
2
X
89
trip measuring system E
2
X
90
trip l>
2
X
91
trip l>>
2
X
92
trip IN>
2
X
93
trip IN>>
2
X
Auto-reclosure indications
Fun
128 160 176 192 254 255
Inf Description
GI Type
t(z) l>>
∆l
T
∆l
L
GEN GLB
128 CB 'on' by AR
1
X
X
X
129 CB 'on' by long-time AR
1
X
X
X
130
AR
blocked
X 1 X X X
Measurands
Fun
128 160 176 192 254 255
Inf Description
GI Type
t(z) l>>
∆l
T
∆l
L
GEN GLB
144 measurand I
3.1
X
X
145 measurands I, V
3.2
X
X