Configuring the MVI69-103M Module

MVI69-103M ♦ CompactLogix or MicroLogix Platform

IEC 60870-5-103 Master Communication Module

ProSoft Technology, Inc.

Page 27 of 131

November 3, 2008

2.5.10 Class 2 Pend Delay

0 to 2^32-1

This parameter sets the minimum number of milliseconds to delay between class
2 polls for pending data.

2.5.11 Class 1 Poll Delay

0 to 2^32-1

This parameter sets the minimum number of milliseconds to delay between each
class 1 poll.

2.5.12 Class 2 Poll Delay

0 to 2^32-1

This parameter sets the minimum number of milliseconds to delay between each
class 2 poll.

2.5.13 Auto Clock Req Mode

0=Sync Only, 1=Load delay/sync, 2=Acquire delay/load delay/sync

This parameter specifies the method used to perform automatic clock
synchronization. 0 performs a synchronization without delay, 1 performs
synchronization using the fixed Propagation Delay and 2 computes the delay and
use this value when synchronization takes place.

2.5.14 Propagation Delay

0 to 65535

This parameter sets the fixed propagation delay to be utilized if the Auto Clock
Req Mode parameter is set to a value of 1.

2.5.15 Response Timeout

0 to 2^32-1 milliseconds

This parameter sets the maximum number of milliseconds to wait for a
confirmation from the controlled station to a request from this module.

2.5.16 ACTTERM with setpoint

Yes or No

This parameter determines if an ACTTERM will be sent. If the parameter is set to
Yes, then setpoint commands will issue an ACTTERM when the command is
complete. If the parameter is set to No, ACTCON is the last response to a
setpoint command.