ProSoft Technology MVI69-103M User Manual

Page 109

Advertising
background image

Reference MVI69-103M

♦ CompactLogix or MicroLogix Platform

IEC 60870-5-103 Master Communication Module

ProSoft Technology, Inc.

Page 109 of 131

November 3, 2008

Fun

128 160 176 192 254 255

Inf Description

Com Type

t(z) l>>

∆l

T

∆l

L

GEN GLB

24

activate characteristic 2

On

20

X

25

activate characteristic 3

On

20

X

26

activate characteristic 4

On

20

X

Generic functions

Fun

128

160

176

192

254

255

Inf

Description

Type

t(z)

l>>

∆l

T

∆l

L

GEN GLB

240 read headings of all defined groups

21

X

241 read values or attributes of all entries of

one group

21

X

243 read directory of a single entry

21

X

244 read value or attribute of a single entry

21

X

245 general interrogation of generic data

21

X

248 write entry

10

X

249 write entry with confirmation

10

X

250 write entry with execution

10

X

251 write entry abort

10

X

5.7.6 Definition

and

Presentation of ASDUs In Monitor Direction

Type 1: Time-tagged

Bytes Description

Spec

1

Value of 1

1 0x81

1 COT

1

Common address of ASDU

1 Function

Type

1 Information

number

1

DPI (0 to 3)

7.2.6.5

4

4-octet binary time

7.2.6.28

1 SIN

7.2.6.23

Type 2: Time-tagged with relative time

Bytes Description

Spec

1

Value of 2