background image

MVI69-103M ♦ CompactLogix or MicroLogix Platform

Configuring the MVI69-103M Module

IEC 60870-5-103 Master Communication Module

Page 28 of 131

ProSoft Technology, Inc.

November 3, 2008

2.6

[IEC-103 Master Session x Sector y]

Within each session definition, is a parameter that specifies the number of
sectors for the session. For each sector defined for a session, there must exist a
[IEC-103 Master Session x Sector y] section. Where the x value represents the
session index and the y value represents sector index. For example if session 0
contains 1 sector, there must be a section with the following name in the
configuration file: [IEC-103 Master Session 0 Sector 0].

2.6.1 Common ASDU Address

0 to 255

This parameter sets the common ASDU address to association with this sector of
the specified session. This parameter is usually set the same as the data link
address when only one sector is used.

2.6.2 Online Time Sync.

Yes or No

This parameter specifies if the sector in the controlled device will be sent a time
synchronization command when the unit is first recognized as being online. This
should only be used for devices that do not send an EOI message after
initializing.

2.6.3 Online

General

Int

Yes or No

This parameter specifies if the sector in the controlled device will be sent a
general interrogation command when the unit is first recognized as being online.
This should only be used for devices that do not send an EOI message after
initializing.

2.6.4 EOI

Time

Sync.

Yes or No

This parameter specifies if the sector in the controlled device will be sent a time
synchronization command after this module received an EOI message from the
controlled unit.

2.6.5 EOI General Int

Yes or No

This parameter specifies if the sector in the controlled device will be sent a
general interrogation command after this module received an EOI message from
the controlled unit.