Mvi69-103m status data area, Mvi69-103m, Status data area – ProSoft Technology MVI69-103M User Manual

Page 95

Advertising
background image

Reference MVI69-103M

♦ CompactLogix or MicroLogix Platform

IEC 60870-5-103 Master Communication Module

ProSoft Technology, Inc.

Page 95 of 131

November 3, 2008

5.3.5 DB9 to RJ45 Adaptor (Cable 14)

5.4 MVI69-103M

Status

Data

Area

This section contains a listing of the data contained in the MVI69-103M status
data object, configuration error word and module error codes.

5.4.1 MVI69-IEC

60870-5-103

Master Communication Module

Error/Status Data Format

Offset Parameter Description

0 Scan

Count

This status value contains a counter incremented on each scan of the
module's main loop.

1 to 2

Product Name This two-word data area contains the text values representing the

product name. These words contain the text 'I3M5' for the MVI69
platform.

3 to 4

Revision

This two-word data area contains the text values for the revision
number.

5 to 6

Op Sys #

This two-word data area contains the text values for the operating
system number.

7 to 8

Run Number

This two-word data area contains the text values for the run number.

9

Read Blk Cnt

This word contains the total number of block read operations
successfully executed.

10

Write Blk Cnt

This word contains the total number of block write operations
successfully executed.

11

Parse Blk Cnt

This word contains the total number of write blocks successfully
parsed.

12

Error Blk Cnt

This word contains the total number of block transfer errors.

13

Event Msg Cnt This word contains the number of event messages waiting to send to

the processor.

14

Event Msg
Overflow

This word contains a value of 0 if the event message buffer has not
overflowed. If the event buffer overflows, this word will be set to a
value of 1.

Advertising