ProSoft Technology MVI69-103M User Manual

Page 112

Advertising
background image

MVI69-103M ♦ CompactLogix or MicroLogix Platform

Reference

IEC 60870-5-103 Master Communication Module

Page 112 of 131

ProSoft Technology, Inc.

November 3, 2008

Type 9: Measurands II

Bytes Description

Spec

1

Value of 9

1

I = 1 to 9 for number of values

1 COT

1

Common address of ASDU

1 Function

Type

1 Information

number

2 Current

L

1

7.2.6.8

2 Current

L

2

7.2.6.8

2 Current

L

3

7.2.6.8

2 Voltage

L

1 to E

7.2.6.8

2 Voltage

L

2-E

7.2.6.8

2 Voltage

L

3-E

7.2.6.8

2

Active power P

7.2.6.8

2

Reactive power Q

7.2.6.8

2 Frequency

f

7.2.6.8

Value of I determines number of parameters passed in the message with a range
of 1 to 9 but always starts with the L

1

value.

5.7.7 Definition

and

Presentation Of ASDUs In Control Direction

Type 6: Time synchronization

Bytes Description

Spec

1

Value of 6

1 0x81

1 COT

1

Common address of ASDU

1

Function Type = GLB (255)

1 Information

number

7 7-Octet

binary

time

7.2.6.29

Type 7: Initiation of general interrogation

Bytes Description

Spec

1

Value of 7

1 0x81

1 COT

1

Common address of ASDU

1

Function Type = GLB (255)

1 Information

number

1

SCN (scan number 0 to 255)

7.2.6.21

Advertising