INTEROPERABILITY

5.8.1 Physical

Layer

5.8.2 Electrical

Interface

⌧ EIA RS-485

⌧ Number of loads 32. For one protection equipment

NOTE - EIA RS-485 standard defines unit loads so that 32 of them can be operated on one line.
For detailed information refer to clause 3 of EIA RS-485 standard.

5.8.3 Optical

Interface

Glass fiber

Plastic fiber

F-SMA type connector

BFOC/2,5 type connector

5.8.4 Transmission

speed

⌧ 9 600 bit/s

⌧ 19 200 bit/s

5.8.5 Link

Layer

There are no choices for the link layer.

5.8.6 Application

Layer

5.8.7 Transmission mode for application data

Mode 1 (least significant octet first), as defined in 4.10 of IEC 60870-5-4, is used
exclusively in this companion standard.

5.8.8 Common Address of ASDU

⌧ One Common Address of ASDU (identical with station address)