Diagnostics and Troubleshooting

MVI69-103M ♦ CompactLogix or MicroLogix Platform

IEC 60870-5-103 Master Communication Module

ProSoft Technology, Inc.

Page 65 of 131

November 3, 2008

Key Interval

[6] 5

milliseconds

ticks

[7]

10 milliseconds ticks

[8]

50 milliseconds ticks

[9]

100 milliseconds ticks

[0]

Turn off timing marks

Removing Timing Marks in the Data Analyzer

Press [0] to turn off timing marks in the Data Analyzer screen.

Viewing Data in Hexadecimal Format

Press [H] to display the data on the current page in hexadecimal format.

Viewing Data in ASCII (Text) Format

Press [A] to display the data on the current page in ASCII format. This is useful
for regions of the database that contain ASCII data.

Starting the Data Analyzer

Press [B] to start the data analyzer. After the key is pressed, all data transmitted
and received on the currently selected port will be displayed. The following
illustration shows an example.

The Data Analyzer displays the following special characters:

Character Definition

[ ]

Data enclosed in these characters represent data received on the port.

< >

Data enclosed in these characters represent data transmitted on the port.

<R+>

These characters are inserted when the RTS line is driven high on the port.

<R->

These characters are inserted when the RTS line is dropped low on the port.

<CS>

These characters are displayed when the CTS line is recognized high.

_TT_

These characters are displayed when the timing mark interval has been reached.
This parameter is user defined.