Ladder Logic

MVI69-103M ♦ CompactLogix or MicroLogix Platform

IEC 60870-5-103 Master Communication Module

ProSoft Technology, Inc.

Page 49 of 131

November 3, 2008

3.3

Adding the Module to an Existing MicroLogix Project

If you are installing and configuring the module with a MicroLogix processor,
follow these steps. If you are using a CompactLogix processor, refer to the
previous section.

The first step in setting up the processor ladder file is to define the I/O type
module to the system. Start RSLogix 500, and follow these steps:

1 In RSLogix, open your existing application, or start a new application,

depending on your requirements.

2 Double-click the I/O Configuration icon located in the Controller folder in the

project tree. This action opens the I/O Configuration dialog box.

3 On the I/O Configuration dialog box, select "Other - Requires I/O Card Type

ID" at the bottom of the list in the right pane, and then double-click to open
the Module dialog box.