ProSoft Technology MVI69-103M User Manual

Page 81

Advertising
background image

Reference MVI69-103M

♦ CompactLogix or MicroLogix Platform

IEC 60870-5-103 Master Communication Module

ProSoft Technology, Inc.

Page 81 of 131

November 3, 2008

If Block Transfer Size = 240:

Write Block

These blocks of data transfer information from the CompactLogix or MicroLogix
processor to the module. The structure of the output image used to transfer this
data is shown in the following table.

Offset Description

Length

0

Write Block ID

1

1 to n

Write Data

n

where

n = 60, 120, or 240 depending on the Block Transfer Size parameter (refer to the
configuration file).

The Write Block ID is an index value used to determine the location in the
module's database where the data will be placed.

How Data is Transferred

In order to understand how the data is transferred between the processor and the
module, you must understand the Read Data and Write Data area concept in the
module's database. The module's database can be partially, or totally divided into
Read Data Areas and Write Data Areas.

These areas are defined by the user when the configuration file is being edited.
The following parameters define the Read and Write data areas:

Advertising