ProSoft Technology MVI69-103M User Manual
Page 119

Reference MVI69-103M
♦ CompactLogix or MicroLogix Platform
IEC 60870-5-103 Master Communication Module
ProSoft Technology, Inc.
Page 119 of 131
November 3, 2008
5.8.22 Basic application functions
⌧
Test mode
⌧
Blocking of monitor direction
Disturbance data
Generic services
⌧
Private data (if ASDU type is supported by module)
5.8.23 Miscellaneous
Measurands are transmitted with ASDU 3 as well as with ASDU 9. As defined in
7.2.6.8, the maximum MVAL can either be 1,2 or 2,4 times the rated value. No
different rating shall be used in ASDU 3 and ASDU 9, that is, for each
measurand there is only one choice.
Measurand
Max. MVAL = rated value times
1,2
or
2,4
Current L
1
⌧
⌧
Current L
2
⌧
⌧
Current L
3
⌧
⌧
Voltage L
1-E
⌧
⌧
Voltage L
2-E
⌧
⌧
Voltage L
3-E
⌧
⌧
Active power P
⌧
⌧
Reactive power Q
⌧
⌧
Frequency f
⌧
⌧
Voltage L
1
- L
2
⌧
⌧